Product Details
I. Product Description
This current transformer is a current data acquisition product designed for low-voltage (LV) lines. Featuring a split-core structure, it is primarily used for indoor busbar systems. It can be installed on lines by phase to achieve low-voltage branch current data acquisition.
II. Performance Parameters
Category | Project | Parameters | Remarks |
Electrical parameters | Rated current range | 50 ~4000A | / |
Output current | 1A /5A | / | |
Input frequency | 50 /60Hz | / | |
Accuracy level | 0.5S ~Level 1 | / | |
Output load | 1 ~10VA | / | |
Performance parameters | Working environment temperature | -25 ~70 degrees | / |
Storage temperature | -40 ~70 degrees | / | |
Insulation voltage | AC3000V | / | |
Insulation strength | 500M Ω/500V/min | / | |
Shell material | alloy (ABS+PC), fire rating 94-V0 | / | |
standard | GB /T20840.1.2 | / | |
III. Dimensional Drawing (Unit: mm)
Inner diameter | A | B | C | D | E | F |
RDP23 | 84 | 97 | 54 | 36 | 24 | 34 |
RDP58 | 114 | 147 | 54 | 36 | 54 | 84 |
RDP88 | 144 | 147 | 54 | 36 | 84 | 84 |
RDP510 | 114 | 167 | 54 | 36 | 54 | 104 |
RDP812 | 144 | 187 | 54 | 36 | 84 | 124 |
RDP816 | 144 | 223 | 54 | 36 | 84 | 164 |


ZH