Product Details
I. Product Overview
This product is a split-core current transformer designed for measuring cable line currents. The input cable passes through the central aperture of the device, and a secondary current is output at a specific ratio. By connecting a sampling resistor in series at the output terminal, the current signal can be converted into a voltage signal.
II. Electrical Parameters
Project | Parameters | Remarks | |
Electrical parameters | Primary current | 1 ~125A | / |
Secondary current and current | 0.4 ~50mA | / | |
Maximum primary current | 150A | / | |
Load resistor | <20 Ω | / | |
ratio difference | <0.5 (rated 5%~max) | / | |
angular difference | <100 (rated 5%~max) | / | |
Input frequency | 50 ~60Hz | / | |
Performance parameters | Operating temperature | -25 ~75 degrees | / |
power frequency withstand voltage | AC4000V | / | |
Shell | Black PC | / | |
Output | Output terminals can be customized | / |
III. Dimensional Drawing (Unit: mm)