I. Product Overview
To establish an energy efficiency index monitoring system for distribution transformers, operational data is collected through smart devices such as wireless current transformers and smart integrated terminals. This allows for the analysis of whether the losses of high-efficiency energy-saving distribution transformers meet the required standards after commissioning.
Wireless smart CTs are installed on the high-voltage (HV) side of the distribution transformer to collect HV current signals. The AC sampling function of the smart integrated terminal (or other terminals) collects low-voltage (LV) side data, including current, voltage, power, and electrical energy. The terminal gathers measurement data output by the wireless smart CTs, which can effectively monitor electricity theft, calculate transformer loss data, and upload it to the master station.
II. Electrical Parameters
Project | Parameters | Remarks | |
Electrical parameters | Current ratio | 630A : 157.5mA | / |
Rated current | 630A | / | |
Current ratio | 4000 1. | can be defined according to customer requirements. | |
Maximum current | 756A | / | |
Input frequency | 50 /60Hz | / | |
Ratio linearity | ± 0.2% | / | |
Performance parameters | Flame retardant grade | UL94-V0 | / |
Operating temperature | -40 ~75 degrees | / | |
Relative humidity | <; 95% RH | / | |
Waterproof rating | IP67 | / | |
Corrosion resistance | Intermediate salt spray for 24 hours | / | |
Tensile strength | When used with a rubber pad, the lateral tensile strength is>50N | / | |
Part parameters | Shell material | PC +Fiberglass | / |
Magnetic core cross-section | 10 *10mm | / | |
Magnetic core material | Permalloy | / | |
Pressure spring material | 304 Stainless steel | / |
III. Dimensional Drawing (Unit: mm)


ZH