Product Details
I. Product Overview
Designed for short-circuit and ground fault monitoring and alarming in 5–35 kV overhead distribution line systems for overhead fault indicators. It features real-time online measurement of phase line currents and ground currents. The acquisition unit is equipped with micro-power wireless communication, and the concentrator unit can upload fault information to the master station via a 4G wireless network to achieve fault identification and localization.
This product is designed as a companion for the acquisition unit of overhead line fault indicators, enabling the rapid localization of line fault types and positions while recording fault waveforms. Improved stability of electric field sampling enhances the accuracy of fault diagnosis. The product features an integrated structural design and advanced manufacturing and control processes, effectively ensuring product consistency and reliability. This series of products fully complies with the relevant requirements of the 2019 State Grid Corporation of China (SGCC) Technical Specifications for Bidding of Distribution Line Fault Indicators.
II. Electrical Parameters
Category | Project | Parameters | Remarks |
Electrical parameters | Typical current sampling accuracy | <; ± 0.5% (in conjunction with panel testing) | / |
Power supply CT | with a cross-sectional area of 10 * 20mm, made of Permalloy, 300 turns | optional 10 * 10mm magnetic core | |
Power supply capability | Input current 1A Load 1.8k Ω, output voltage>3.1V | / | |
Thermistors | NTC Thermistor, B3950100K Ω | Optional components | |
Protective ability | IP68 (30 hours at a depth of 1.5 meters) | / | |
Flame retardant rating | UL94-V0 | / | |
Impact resistance | can withstand 3 drops of 1.0 meter without breakage | / | |
card wire grip | used in conjunction with rubber pads, the lateral tension of the wire spring is ≥ 50N, and the longitudinal tension is greater than 100N. | / | |
Rust prevention ability | Intermediate salt spray 96 hours | / | |
Working temperature | -40 ~75 degrees | / | |
Relative humidity | <; 95% RH | / | |
Altitude | <; 4000 meters | / | |
Other parameters | Main shell material | PC +Fiberglass | / |
Spring material | 304 Stainless steel | / | |
installation method | cup installation | / | |
electric field measurement method | metal electric field sheet+electric field PCB | / | |
ROHS The standard | meets the requirements of the "Management Measures for the Restriction of Hazardous Substances in Electrical and Electronic Products" issued by the Ministry of Industry and Information Technology of the People's Republic of China and eight other ministries in 2016, and also fully complies with the requirements of the EU RoHS V2.0 or above standards | / |
III. Dimensional Drawing (Unit: mm)


ZH
EN