Product Details
I. Product Overview
The Motorized High-Precision Energy Harvesting Module for Transient Waveform Recording is designed for short-circuit and ground fault monitoring and alarming in 5–35 kV overhead distribution line systems. It features real-time online measurement of phase line currents and ground currents. The acquisition unit is equipped with micro-power wireless communication, and the concentrator unit can upload fault information to the master station via a 4G wireless network to achieve fault identification and localization.
This product is designed as a companion for the acquisition unit of overhead line fault indicators, enabling the rapid localization of line fault types and positions while recording fault waveforms. Improved stability of electric field sampling enhances the accuracy of fault diagnosis. The product utilizes a motorized installation method to protect the cables, and advanced manufacturing and control processes effectively ensure product consistency and reliability. This series of products fully complies with the 2019 State Grid Corporation of China (SGCC) Technical Specifications for Bidding of Distribution Line Fault Indicators and the specific requirements of the Shanghai region.
II. Electrical Parameters
Category | Project | Parameters | Remarks |
Electrical parameters | Current sampling | <; ± 0.2% (in conjunction with board testing) | / |
Typical accuracy | |||
CT | cross-sectional area of 10 * 20mm, material nanocrystals, 300 turns | optional 10 * 10mm magnetic core | |
Tag9 has a power supply capacity of | . The input current is 1A, the load is 1.8k Ω, and the output voltage is>3.1V | / | |
The thermistor | NTC Thermistor, B3950100K Ω | Optional components | |
Protective ability | IP68 (1.5 meters deep for 30 hours) | / | |
Flame retardant rating | UL94-V0 | / | |
Impact resistance | can withstand 3 drops of 1.0 meter at 0 degrees without breakage | / | |
card wire grip | used in conjunction with rubber pads, with a lateral tension of the wire spring ≥ 50N and a longitudinal tension of ≥ 50N. The pulling force is greater than 120N. | / | |
Rust prevention ability | Intermediate salt spray 96 hours | / | |
Working temperature | -40 ~75 degrees | / | |
Relative humidity | <; 95% RH | / | |
Altitude | <; 4000 meters | / | |
Other parameters | Main shell material | PC +Fiberglass | / |
Spring material | 304 Stainless steel | / | |
installation method | electric installation tool installation | / | |
transparent cover screw torque | 7.5 ~8kgf.cm, Use diagonal fixing method to fasten | / | |
electric field measurement | metal electric field pieces | / | |
rubber pads | outer diameter 11-22mm cable (with rubber) installation thick rubber pads. | / | |
ROHS | meets the requirements of the "Management Measures for the Restriction of Hazardous Substances in Electrical and Electronic Products" issued by the Ministry of Industry and Information Technology of the People's Republic of China and eight other ministries in 2016, and also fully complies with the requirements of the EU RoHS 2.0 or higher standards. | / |
III. Dimensional Drawing (Unit: mm)

ZH
EN